ARTICLE 6. CROSS CONNECTIONS
15-601. GENERAL INFORMATION.
(a) Purpose. The purpose of this article is:
(1) To protect the public potable water supply of the city from pollution or contamination due to cross connection;
(2) To prohibit and eliminate all cross connections within the public potable water supply system; and,
(3) To provide for the maintenance of a continuing effective cross connection control program and thus protect the public health.
(b) Responsibility. The city superintendent shall be responsible for effectively conducting the cross connection control program of the city public potable water supply. If in the judgment of the superintendent an approved back flow prevention device is required the superintendent or his or her agent will give notice in writing to the customer to install the proper device. The customer shall immediately install the proper device at the customer’s expense. Failure to comply shall be grounds for discontinuing water service to the customer until the device is properly installed. (Ord. 829, Sec. 1)
15-602. DEFINITIONS.
(a) Agency - The department of the municipal government or water purveyor invested with the responsibility for enforcement of this article.
(b) Air Gap - The unobstructed vertical distance at least twice the diameter of the supply line and no less than one inch, through the free atmosphere between the lowest opening from any pipe or faucet supplying water to a tank, plumbing fixture, or other device and the flood level rim of the receptacle.
(c) Approved Device - Devices tested and accepted by a recognized testing laboratory approved by the Kansas Department of Health and Environment and the superintendent.
(d) Backflow - The flow of water or other substances into the distribution system of a potable supply of water from any source other than its intended source. Backsiphonage is one type of backflow.
(e) Backflow Preventer - A device or means to prevent backflow.
(f) Backsiphonage - The flowing back of contaminated or polluted substances from a plumbing fixture or any vessel or source into the potable water supply system due to negative pressure in the system.
(g) Contaminant - Any substance that upon entering the potable water supply would tender it a danger to the health or life of the consumer.
(h) Cross Connection - Any physical connection or arrangement between two otherwise separate piping system, one of which contains potable water and the other of water or any substance of unknown or questionable quality whereby there may be flow from one system to the other.
(i) Double Check Valve Assembly - A device consisting of two internally loaded soft seated check valves with positive shut-off valves on both upstream and downstream ends, and properly located test ports.
(j) Dual Check Valve - A device consisting of two internally loaded soft seated check valves. This device does not contain test ports and is acceptable for use only at the meter of residential customers.
(k) Free Water Surface - A water surface at atmospheric pressure.
(l) Flood Level Rim - The edge of the receptacle from which water overflows.
(m) Frost Proof Closet - A hopper with no water in the bowl and with the trap and water supply control valve located below frost line.
(n) KDHE - The Kansas Department of Health and Environment.
(o) Plumbing - The practice, materials and fixtures used in the installation maintenance and alteration of all piping fixtures, appliances and appurtenances.
(p) Pollution - The presence of any foreign substance (organic, inorganic or biological) in water which tends to degrade its quality so as to constitute a hazard or impair the usefulness or quality of the water to a degree which does not create an actual hazard to the public health but which does adversely affect the water.
(q) Reduced Pressure Zone Backflow Preventer - An assembly of two independently acting soft seated approved check valves together with a hydraulically operating mechanically independent differential pressure relief valve located between the check valves and at the same time below the first check valve. The unit shall contain properly located test cocks and resilient seated shut-off valves at each end of the assembly. To be approved these assemblies must be accessible for inspection and testing and be installed in an above ground location where no part of the assembly will be submerged.
(r) Tester - A trained technician certified in the testing and repair of backflow preventers.
(s) Vacuum - Any absolute pressure less than that exerted by the atmosphere.
(t) Vacuum Breaker - A device that permits entrance of air into the water supply distribution line to prevent backsiphonage.
(u) Water, Potable - Water free from impurities in amounts sufficient to cause disease or harmful physiological effects. Its quality shall conform to Kansas Department of Health and Environment requirements for public water supplies.
(v) Water, Non-Potable - Water that is not safe for human consumption or that is of questionable potability.
(Ord. 829, Sec. 2)
15-603. REQUIREMENTS.
(a) General. A public potable water supply system shall be designed, installed and maintained in such a manner as to prevent contamination from non-potable sources through cross-connections or any piping connection to the system.
(b) Cross Connections Prohibited. Cross connections are prohibited except when and where as approved by the water superintendent and suitable backflow preventers are properly installed, tested, and maintained to insure proper operation on a continuing basis.
(c) Interconnections. Interconnections between two or more public water supplies shall be permitted only with the approval of the Kansas Department of Health and Environment. (K.S.A. 65-163[a])
(d) Individual Water Supplies. Connections between a private water supply and the public potable water are prohibited. (K.S.A. 65-163[a])
(e) Connections to Boilers. Potable water connections to boiler feed water systems in which boiler water conditioning chemicals are or can be introduced shall be made through an air gap or through a reduced pressure zone principle backflow preventer located in the potable water line before the point where such chemicals may be introduced.
(f) Prohibited Connections. Connection to the public potable water supply system for the following is prohibited unless properly protected by the appropriate backflow prevention device.
(1) Bidets.
(2) Operating, dissection, embalming, and mortuary tables or similar equipment in such installations the hose used for water supply shall terminate at least 12 inches away from every point of the table or attachments.
(3) Pumps for non-potable substances. Priming connections only through an air gap.
(4) Building drainage, sewer, or vent systems.
(5) Commercial buildings or Industrial plants manufacturing or otherwise using polluting or contaminating substances.
(6) Any fixture of similar hazard.
(g) Refrigeration Unit Condensers and Cooling Jackets. Except when potable water provided for a refrigeration condenser or cooling jacket is entirely outside the piping or tank containing a toxic refrigerant, the inlet connection shall be provided with an approved backflow preventer. Heat exchangers used to heat water for potable use shall be of the double wall type.
(h) Protective Devices Required. The type of protective device required under this article shall be determined by the degree of hazard which exists as follows:
(1) Premises having auxiliary water supply shall protect the public system by either an approved air gap or an approved reduced pressure principle backflow prevention assembly.
(2) Premises having water of substances which would be nonhazardous to the health and well-being of the consumers shall protect the public system with no less than an approved double check valve assembly.
(3) Premises where material dangerous to health is handled in a manner which creates an actual or potential hazard shall protect the public system by an approved air gap or an approved reduced pressure principle backflow prevention assembly.
(4) Premises where cross connections are uncontrolled shall protect the public water supply by installing an approved air gap or an approved reduced pressure principle backflow prevention device at the service connection.
(5) Premises where because of security requirements or other prohibitions it is impossible to complete an in plant cross connection inspection, the public system shall be protected by an approved air gap or an approved reduced pressure principle backflow prevention assembly.
(i) Installation. Approved devices shall be installed at all fixtures and equipment where backflow or backsiphonage may occur and where a minimum air gap between the potable water outlet and the fixture or equipment flood level rim cannot be maintained. Backflow and backsiphonage devices of all types shall be in an accessible location. Installation in pits or any other location not properly drained shall be prohibited, except that dual check valves may be installed in the meter box.
(1) Connections not subject to back pressure. Where a water connection is not subject to back pressure, a vacuum breaker shall be installed on the discharge side of the valve on the line serving the fixture or equipment. A list of some conditions requiring protective devices of this kind are given in the following table titled "Cross Connections where Protective Devices are required".
FIXTURES OR EQUIPMENT |
METHOD OF INSTALLATION |
---|---|
Aspirators and ejectors |
C-L at least 6 in. above flood level of receptacle served. |
Dental units |
On models without built-in vacuum breakers--C-L at least 6 in. above flood level rim of bowl. |
Commercial dishwashing machines |
C-L at least 6 in. above flood level of machines. Installed on both hot and cold water supply lines. |
Garbage can cleaning machines |
C-L at least 6 in. above flood level of machine. Installed on both hot and cold water supply lines. |
Hose outlets |
C-L at least 6 in. above highest point on hose line |
Commercial laundry machines |
C-L at least 6 in. above flood level of machine. Installed on both hot and cold water supply lines. |
Lawn sprinklers |
C-L at least 6 in. above highest sprinkler head or discharge outlet, except that the same is not required if the sprinkler system is an above-ground system as it is then exempt from this requirement. |
Steam tables |
C-L at least 6 in. above flood level rim. |
Tanks and vats |
C-L at least 6 in. above flood level rim or line. |
Trough urinals |
C-L at least 30 in. above perforated flush pipe. |
Flush tanks |
Equipment with approved ball cock, installed according to manufacturer’s instructions. |
Hose bibs |
C-L at least 6-in. above flood level of receptacle served. |
(2) Connections Subject to Backpressure. Where a potable water connection is made to a line, fixture, tank, vat, pump, or other equipment with a hazard of backflow or backpressure, and an air gap cannot be installed, the water superintendent may require the use of an approved reduced pressure principle backflow preventer. A partial list of such connections is shown in the following table "Partial List of Cross Connections Subject to Back Pressure".
Chemical lines |
Pumps |
Dock water outlets |
Steam lines |
Individual water supplies |
Swimming pools |
Industrial process water lines |
Tanks and Vats – bottom inlets |
Pressure tanks |
Hose bibs |
(3) Barometric Loop. Water connections where an actual or potential backsiphonage hazard exists may in lieu of devices specified above with a barometric loop. Barometric loops shall precede the point of connection.
(4) Dual Check Valve. Dual check valves may be installed at the meter. These valves shall be inspected and repaired not less frequent than every third year. These valves shall be installed only in situations where the water superintendent is assured that only non-contaminating substances are subject to backflow into the potable system.
(5) Vacuum Breakers. Atmospheric vacuum breakers shall be installed with the critical level at least six inches above the flood rim of the fixture they serve and on the discharge side of the last control valve to the fixture. No shut off valve or faucet shall be installed beyond the atmospheric vacuum breaker. Pressure vacuum breakers shall be installed with the critical level at least 12 inches above the flood rim but may have control valves downstream from the vacuum breaker. For closed equipment or vessels such as pressure sterilizers the top of the vessel shall be considered the flood level rim and a check valve shall be installed on the discharge side of the pressure vacuum breaker.
(Ord. 2005-03; Ord. 829, Sec. 4; Code 2008)
15-604. MAINTENANCE AND REPAIR.
It shall be the responsibility of building and premise owners to maintain all backflow preventers and vacuum breakers within the building or on the premises in good working order and to make sure no piping or other arrangements have been installed for the purpose of bypassing the backflow devices. Testing and repair of these devices should be made by qualified technicians. (Qualified technicians are those technicians who have completed a Kansas Department of Health and Environment approved training course and have passed a written examination such as the American Backflow Prevention Association device tester’s examination.) The water superintendent shall certify the device testers after ascertaining the technician meets the above qualifications. The water superintendent will also assure the proper installation of all backflow preventers and will set appropriate testing and overhaul schedules for such devices. Testing intervals shall not exceed one year and overhaul intervals shall not exceed five years.
(a) Certified Tester/Repair Technicians. All certified tester/repair technicians shall be re-certified at no less than three year intervals. Persons certified as tester/repair technicians at the time of the adoption of this article shall continue to be certified for a period of no more than three years as determined by the city superintendent. (Ord. 829, Sec. 5)
15-605. PENALTIES AND FINES.
Notification. It shall be unlawful for any citizen to violate any of the provisions of this article. The city superintendent shall notify the owner, or authorized agent of the owner, of a building or premises in which there is found a violation of this article, of such violation. The superintendent shall set a reasonable time for the owner to have the violation corrected. If the owner fails to correct the violation within the specified time, the superintendent shall cease delivery of water to the building or premises until the violation shall be satisfactorily corrected. In addition, the city superintendent may cause a complaint to be filed against the violator with the Nickerson municipal court. If found guilty, a violator shall be fined an amount between $25.00 and $100.00 at the discretion of the judge. (Ord. 829, Sec. 6)