14.05.2113.9 Masonry chimneys—Termination.
Section 2113.9 (Termination) of the IBC shall be replaced with the following:
Termination. Chimneys shall extend at least 2 feet (610 mm) higher than any portion of the building within 10 feet (3048 mm), but shall not be less than 3 feet (914 mm) above the highest point where the chimney passes through the roof. In those areas designated as Wildland Urban Interface/Intermix by CCC 15.13.030, chimney outlets shall not be located within 15 feet of obstructions, other buildings, vegetation or other combustible material.
(Sec. 3 (Exh. B) of Ord. 2004-06-04)