15.12.903.3.9 Addition of Section 903.3.9.
A new Section 903.3.9 of the International Fire Code shall be added to read as follows:
903.3.9 Sprinkler system indicating valves. Sprinkler system indicating valves for sprinkler systems installed in other than one or two family dwellings and small systems consisting of fewer than 100 heads shall be wall or post-indicating valves unless the control valves are located in a room with direct access to the exterior of the building within five feet of the sprinkler riser. Where direct access to the building exterior is provided in lieu of wall or post-indicating valves, the exterior of the access door shall be clearly labeled with a sign (or other approved means) consisting of letters not less than 6 inches in height with a 3/4 inch stroke on a contrasting background stating “Sprinkler Control Valves.” Such access door shall normally be locked but shall be opened from the outside by placing keys to the locking mechanism in a security box meeting the requirements of Section 506.
(Sec. 20 of Ord. 1996-02-02; amended by Sec. 1 (Exh. A) of Ord. 2004-06-05; amended by Sec. 27 of Ord. 2016-07-02. Formerly 15.12.903.3.1.1.2)