Chapter 17.52
FIRE PROTECTION EQUIPMENT

Sections:

17.52.010    Hydrants.

17.52.020    Fire extinguishers.

17.52.030    Fire department approval.

17.52.010 Hydrants.

In every mobile home park that contains twenty or more mobile home lots there shall be installed a minimum of one standard approved fire hydrant within the confines of the park. Additional fire hydrants shall be required so as not to exceed five hundred foot spacing. All hydrants shall be supplied with water from an approved six inch water main. (Prior code § 17.52.010)

17.52.020 Fire extinguishers.

There shall be installed and maintained in a conspicuous and accessible location in every trailer park containing three or more cabanas at least one approved two and one-half gallon portable fire extinguisher or equivalent. Additional approved extinguishers shall be installed at distances of not more than two hundred feet apart. Alternatives to the requirements of this section may be authorized by the local fire department. (Prior code § 17.52.020)

17.52.030 Fire department approval.

All first aid fire protection equipment required by this title shall meet the approval of the fire department. (Prior code § 17.52.030)