Chapter 13.06
CROSS-CONNECTION CONTROL REGULATIONS

Sections:

13.06.100    Abbreviations and acronyms.

13.06.110    Definitions.

13.06.120    Applicability.

13.06.130    Purpose.

13.06.140    Responsibility.

13.06.150    General requirements.

13.06.160    Enforcement.

13.06.170    Civil penalty.

13.06.180    Operating policies.

13.06.100 Abbreviations and acronyms.

A.    DOH – Washington State Department of Health.

B.    RCW – Revised Code of Washington (laws of the state).

C.    WAC – Washington State Administrative Code. (Ord. 1416 § 1, 2006)

13.06.110 Definitions.

“Approved air gap” means a physical separation between the free flowing end of a potable water supply pipeline and the overflow rim of an open or nonpressurized receiving vessel. To be an air gap approved by the DOH, the separation must be at least:

A.    Twice the diameter of the supply piping measured vertically from the overflow rim of the receiving vessel, and in no case be less than one inch, when unaffected by vertical surfaces (sidewalls); and

B.    Three times the diameter of the supply piping, if the horizontal distance between the supply pipe and a vertical surface (sidewall) is less than or equal to three times the diameter of the supply pipe, or if the horizontal distance between the supply pipe and intersecting vertical surfaces (sidewalls) is less than or equal to four times the diameter of the supply pipe and in no case less than one and one-half inches.

“Approved atmospheric vacuum breaker” means an atmospheric vacuum breaker of make, model, and size that is approved by the DOH. Atmospheric vacuum breakers that appear on the current approved backflow prevention assemblies list developed by the University of Southern California Foundation for Cross-Connection Control and Hydraulic Research, or that are listed, or approved by other nationally recognized testing agencies (such as the International Association of Plumbing and Mechanical Officials, American National Standards Institute, or Underwriter Laboratories) and acceptable to the local administrative authority are considered approved by the DOH.

“Approved backflow preventer” means an approved air gap, an approved backflow prevention assembly, or an approved atmospheric vacuum breaker, relied upon by the purveyor for the protection of the public water system. The requirements of WAC 246-290-490 do not apply to backflow preventers installed for other purposes.

“Approved backflow prevention assembly” means a reduced pressure backflow assembly, reduced pressure detector assembly, double check valve assembly, double check detector assembly, pressure vacuum breaker assembly, or spill resistant vacuum breaker assembly, of make, model, and size that is approved by the DOH. Assemblies that appear on the current approved backflow prevention assemblies list developed by the University of Southern California Foundation for Cross-Connection Control and Hydraulic Research, or other nationally recognized testing agencies and acceptable to the local administrative authority are considered approved by the DOH.

“Auxiliary water supply” means a water supply, other than the purveyor’s water supply, on or available to the consumer’s premises.

“Backflow” means the undesirable reversal of flow of water or other substances through a cross-connection into the public water system or consumer’s potable water system by means of backpressure or backsiphonage.

“Backpressure” means a pressure (caused by a pump, elevated tank or piping, boiler, or other means) on the consumer’s side of the service connection that is greater than the pressure provided by the public water system and which may cause backflow.

“Backsiphonage” means backflow due to a reduction in system pressure in the purveyor’s distribution system and/or the consumer’s water system.

“Consumer” means any person receiving water from a point of delivery of the public water system. For purposes of cross-connection control, “consumer” means the owner or operator of a premises receiving water from a point on delivery of the public water system.

“Consumer’s water system,” as used in WAC 246-290-490, means any potable and/or industrial water system that begins at a point of delivery from the public water system and is located on the consumer’s premises. The consumer’s water system includes all auxiliary sources of supply, storage, treatment, and distribution facilities, piping, plumbing, and fixtures under the control of the consumer.

“Contaminant” means a substance present in drinking water that may adversely affect the health of the consumer or the aesthetic qualities of the water.

“Cross-connection” means any actual or potential physical connection between a public water system or the consumer’s water system and any source of nonpotable liquid, solid, or gas that could contaminate the potable water supply by backflow.

“Cross-connection control program” means the administrative and technical procedures the water purveyor implements to protect the public water system from contamination via cross-connections as required in WAC 246-290-490.

“Cross-connection control specialist” means a person holding a valid cross-connection control specialist certificate issued by DOH in accordance with Chapter 246-292 WAC.

“Director” means Director of Public Works or duly authorized representative.

“DOH” means the Washington State Department of Health or health officer as identified in a joint plan of operation in accordance with WAC 246-290-030(1).

“High health cross-connection hazard” means a cross-connection that could impair the quality of potable water and create an actual public health hazard through poisoning or spread of disease by a contaminant source.

“Human consumption” means the use of water for drinking, bathing or showering, hand washing, food preparation, cooking, or oral hygiene.

“In-premises protection” means a method of protecting the health of consumers served by the consumer’s potable water system, located within the property lines of the consumer’s premises by the installation of an approved air gap or approved backflow prevention assembly at the point of hazard, which is generally a plumbing fixture.

“Local administrative authority” means the local official, board, department, or agency authorized to administer and enforce the provisions of the Uniform Plumbing Code as adopted under Chapter 19.27 RCW.

“Low health cross-connection hazard” means a cross-connection that could cause an impairment of the quality of potable water to a degree that does not create a hazard to the public health, but does adversely and unreasonably affect the aesthetic qualities of such potable waters.

“Point of delivery” means the point at which the consumer’s water system connects to the public water system.

“Potable” means water suitable for human consumption.

“Premises” means a single building site, or single lot or aggregation of lots tied together by agreement for the purpose of obtaining a building permit or utility service.

“Premises isolation” means a method of protecting a public water system by installation of approved air gap or approved backflow prevention assembly at or near the service connection or alternative location acceptable to the purveyor to isolate the consumer’s water system from the purveyor’s distribution system.

“Public water system” means the water supply source, including all water treatment, storage, transmission and distribution facilities, to the point of delivery to the consumer.

“Purveyor” means the City of Ferndale, owner and operator of the public water system.

“Service connection” means the point of delivery from which potable water is provided to a single-family residence, or other residential or nonresidential population.

“State Board of Health” and “Board” means the board created by RCW 43.20.030.

“Uniform Plumbing Code” means the code adopted under RCW 19.27.031(4) and amended under Chapter 51-46 WAC. This code establishes statewide minimum plumbing standards applicable within the property lines of the consumer’s premises.

“Used water” means water that has left the control of the purveyor. (Ord. 1416 § 1, 2006)

13.06.120 Applicability.

This chapter shall apply to all consumers with service connections to the purveyor’s public water distribution system. (Ord. 1416 § 1, 2006)

13.06.130 Purpose.

A.    Protect the public water system from contamination due to backflow through cross-connections; and

B.    Eliminate or control cross-connections between the public water system and the consumer’s water system. (Ord. 1416 § 1, 2006)

13.06.140 Responsibility.

A.    The consumer’s responsibility for cross-connection control shall begin at the service connection.

B.    Consumers shall be responsible for the:

1.    Elimination of cross-connections when possible; or

2.    Control of cross-connections at the service connection (premises isolation); or

3.    Control of cross-connections, within the consumer’s water system, by relying on in-premises protection when premises isolation is not required by WAC 246-290-490 and this method is approved by the Director.

C.    Consumers are responsible for the installation, testing, inspection, repair, maintenance, and proper operation of approved backflow preventers required for the control of cross-connections between their premises and the public water system. (Ord. 1416 § 1, 2006)

13.06.150 General requirements.

A.    The rules and regulations of the Washington State Department of Health as published in WAC 246-290-490 and hereby adopted by reference as they may be from time to time amended.

B.    Consumers shall comply with the City’s cross-connection control program policies and procedures as they may be from time to time amended.

C.    An approved backflow preventer is required on all private fire lines, appropriate to the assessed degree of cross-connection health hazard, and shall incorporate a water meter for detecting water consumption. The approved backflow preventer shall be placed such that access for the City is provided to physically or electronically read the detecting meter.

D.    Consumer shall permit periodic entry to their premises by a cross-connection control specialist, for the determination of cross-connection health hazards and compliance with cross-connection control requirements. (Ord. 1416 § 1, 2006)

13.06.160 Enforcement.

A.    In the event a consumer fails to comply with cross-connection control requirements, the Director shall have the authority to issue to the consumer a final order to achieve compliance with this chapter, WAC 246-290-490 and or City cross-connection control policy and procedures, extent and time of the violation and the cross-connection control policy and procedures. The order shall include:

1.    A description of the specific damage of the specific damage or potential damage that reasonably might occur;

2.    A notice that the violation cease and desist and, in appropriate cases, the specific corrective actions to be taken;

3.    That water service will be denied until corrective actions are completed or discontinued unless corrective actions are completed within a reasonable time to comply, depending on the circumstances;

4.    The address, telephone number and contact person that the consumer may contact if a dispute exists as to the corrective action required;

5.    That the consumer may request a hearing with the Hearings Examiner;

6.    That the City will charge a shut-off and turn-on fee before service is resumed following discontinuance and/or impose civil penalties;

7.    That the local administrative authority will be notified; and

8.    That the service will not be shut off while a hearing is pending.

B.    The local administrative official shall be notified prior to the City:

1.    Denying water service; or

2.    Discontinuing water service.

C.    When an unprotected connection between the public water system and the consumer’s water system constitutes an imminent threat of contamination to the City’s public water system, water service may be shut off immediately without the notices provided above. In that case, notice of shut-off, corrective action, and appeal procedures and notice to the local administrative official shall be sent immediately upon such action being taken. (Ord. 1416 § 1, 2006)

13.06.170 Civil penalty.

A.    In the event a consumer fails to comply with cross-connection control requirements, the Director shall have the authority to issue to the consumer a notice of violation in accordance with the provisions of Chapter 1.12 FMC ordering compliance with this chapter, WAC 246-290-490 and/or City cross-connection control policy and procedures, extent and time of the violation and the cross-connection control policy and procedures. In addition to the requirements of FMC 1.12.040(B), the notice of violation shall also include:

1.    A description of the specific damage or potential damage that reasonably might occur;

2.    That water service will be denied until corrective actions are completed or discontinued unless corrective actions are completed within a reasonable time to comply, depending on the circumstances;

3.    The address, telephone number and contact person that the consumer may contact if a dispute exists as to the corrective action required;

4.    That the City will charge a shut-off and turn-on fee before service is resumed following discontinuance and/or impose civil penalties;

5.    That the service will not be shut off while a hearing is pending unless there is an imminent threat as set forth in subsection (B) of this section.

B.    When an unprotected connection between the public water system and the consumer’s water system constitutes an imminent threat of contamination to the City’s public water system, water service may be shut off immediately without the notices provided above. In that case, notice of shut-off, corrective action, and appeal procedures and notice to the local administrative official shall be sent immediately upon such action being taken.

C.    In addition to any other remedy or sanction available, a consumer who fails to comply with a notice of violation issued by the Director or Hearings Examiner pursuant to this chapter and/or Chapter 1.12 FMC, or who fails to conform to the terms of an approval issued, shall be subject to civil penalties in accordance with Chapter 1.12 FMC.

D.    Penalties shall be paid to the water fund. (Ord. 1819 § 11, 2013; Ord. 1817 § 2, 2013; Ord. 1416 § 1, 2006)

13.06.180 Operating policies.

The Director shall promulgate and implement the City’s policy on cross-connection control for the operation of the cross-connection control program. The cross-connection control program policy shall be enforced under the requirements of the City’s cross-connection control ordinance. (Ord. 1416 § 1, 2006)