Chapter 21.08
INTERNATIONAL BUILDING CODE

Sections:

21.08.010    International Building Code adopted.

21.08.013    Copies on file.

21.08.014    Administration.

21.08.016    IBC Section 202 amended.

21.08.017    IBC Section 403.4.8.1 amended.

21.08.018    Penetrations.

21.08.020    IBC Section 403.4.8.3 amended.

21.08.025    IBC Section 403.7 added.

21.08.030    IBC Section 405.8 amended.

21.08.035    Repealed.

21.08.040    IBC Section 712.1.3.1 amended.

21.08.050    IBC Section 1104.4 amended.

21.08.055    IBC Section 1608.1 amended.

21.08.060    Repealed.

21.08.070    Penetrations into fire command centers.

21.08.072    IBC Chapter 27 amended.

21.08.075    IBC Chapter 31 amended.

21.08.105    Repealed.

21.08.110    Repealed.

21.08.115    Repealed.

21.08.010 International Building Code adopted.

The 2021 Edition of the International Building Code, as adopted by the State Building Code Council in Chapter 51-50 WAC, as published by the International Code Council, excluding Chapter 1, “Administration,” is adopted, together with the following amendments. The Construction Administrative Code, as set forth in Chapter 21.06, shall be used in place of IBC Chapter 1, Administration. (Ord. 4848 § 26, 2024; Ord. 4751 § 22, 2021; Ord. 4524 § 36, 2016: Ord. 4410 § 6, 2013: Ord. 4246 § 2 (part), 2010: Ord. 4188 § 1, 2009: Ord. 4099 § 3 (part), 2007: Ord. 3946 § 1 (part), 2004)

21.08.013 Copies on file.

The city shall at all times keep on file with the city clerk, for reference by the general public, not less than one copy of the International Building Code. (Ord. 4246 § 2 (part), 2010: Ord. 4208 § 3 (part), 2009)

21.08.014 Administration.

The administrative provisions for the enforcement of the International Building Code are located in Chapter 21.06. (Ord. 4638 § 4, 2018)

21.08.016 IBC Section 202 amended.

Section 202 of the IBC is amended to read:

[F] STANDBY POWER SYSTEM. All references to Standby Power Systems shall be considered to indicate Legally Required Power in accordance with the Washington Cities Electrical, and NFPA 70 (National Electrical Code), and shall be in accordance with Chapter 27 Legally Required Standby Power, as a source of automatic electric power of a required capacity and duration to operate requiring building, hazardous material or ventilation systems in the event of a failure of the primary power. Standby Power Systems are required for electrical loads where interruption of the primary power could create hazards or hamper rescue or fire-fighting operations.

(Ord. 4848 § 27, 2024; Ord. 4751 § 23, 2021; Ord. 4638 § 5, 2018)

21.08.017 IBC Section 403.4.8.1 amended.

Section 403.4.8.1 of the IBC is amended to read:

Equipment Room. If the standby system is a generator set inside a building, the system shall be located in a separate room enclosed with 2-hour fire barriers constructed in accordance with Section 403.4.8.1.1 and Section 707 or horizontal assemblies constructed in accordance with Section 711, or both. System supervision with manual start and transfer features shall be provided at the fire command center.

Exception: In Group I-2, Condition 2, manual start and transfer features for the critical branch of the emergency power are not required to be provided at the fire command center.

(Ord. 4524 § 37, 2016: Ord. 4246 § 2 (part), 2010)

21.08.018 Penetrations.

A new Section 403.4.8.1.1 is added to the IBC to read:

Penetrations. Penetrations into and openings through a room containing a standby power system are prohibited except for required exit doors, equipment and ductwork necessary for heating, cooling or ventilation, sprinkler branch line piping, or electrical raceway serving the standby power system or being served by the standby power system. Such penetrations shall be protected in accordance with Section 714.

Exception: Metallic piping with no joints or openings where it passes through the standby power system room.

(Ord. 4524 § 38, 2016: Ord. 4246 § 2 (part), 2010)

21.08.020 IBC Section 403.4.8.3 amended.

Section 403.4.8.3 of the IBC is amended to read:

403.4.8.3 Standby power loads. The following are classified as standby power loads:

1. Power and lighting for the fire command center required by Section 403.4.6;

3. Ventilation and automatic fire detection equipment for smokeproof enclosures;

4. Smoke control systems.

5. Elevators.

6. Where elevators are provided in a high-rise building for accessible means of egress, fire service access or occupant self-evacuation, the standby power system shall also comply with Sections 1009.4, 3007 or 3008, as applicable.

7. Sump pumps required by ASME A17.1 serving pit drains at the bottom of elevator hoistways of fire service access or occupant evacuation elevators.

8. Fuel-fired emergency generator sets and associated fuel storage, including optional generator sets, located more than 75 feet above the lowest level of Fire Department vehicle access requires the approval of the Fire Code Official.

(Ord. 4751 § 24, 2021; Ord. 4524 § 39, 2016: Ord. 4246 § 2 (part), 2010: Ord. 4099 § 3 (part), 2007: Ord. 3946 § 1 (part), 2004)

21.08.025 IBC Section 403.7 added.

Chapter 4 of the IBC is amended and supplemented by the addition of a new Section 403.7 to read:

403.7 Smoke control. A smoke control system meeting the requirements of Section 909 shall be provided in buildings that exceed ten stories, or contain a use requiring defend-in-place firefighting operations in which occupants of some area cannot readily evacuate that area. This includes portions of facilities housing functions essential to continuity of public safety operations, and Group I and LC Occupancies where in the judgment of the Building Official and Fire Code Official, occupants having limited capacity for self-preservation are located on floors more than 75' above the lowest level of Fire Department vehicle access. A smoke control system for a defend-in-place use may be a performance-based design to protect that use without providing smoke control throughout the entire building, but shall otherwise comply with Section 909.

Exception: Smoke control may be omitted when approved by the Building Official and Fire Code Official.

(Ord. 4524 § 40, 2016: Ord. 4246 § 2 (part), 2010: Ord. 4099 § 3 (part), 2007: Ord. 3946 § 1 (part), 2004)

21.08.030 IBC Section 405.8 amended.

Section 405.8 of the IBC is amended to read:

405.8 Standby Power and emergency power. A standby power system complying with Section 2702 shall be provided for standby power loads specified in Section 405.8.1. An emergency power system complying with Section 2702 shall be provided for the emergency power loads specified in Section 405.8.2.

Fuel-fired emergency generator sets and associated fuel storage, including optional generator sets, located more than 30 feet below the lowest level of exit discharge requires the approval of the Fire Code Official.

(Ord. 4524 § 41, 2016: Ord. 4246 § 2 (part), 2010: Ord. 4099 § 3 (part), 2007: Ord. 3946 § 1 (part), 2004)

21.08.035 IBC Section 501.2 amended.

Repealed by Ord. 4524. (Ord. 4246 § 2 (part), 2010: Ord. 4099 § 3 (part), 2007: Ord. 3946 § 1 (part), 2004)

21.08.040 IBC Section 712.1.3.1 amended.

Section 712.1.3.1 of the International Building Code is hereby amended to read:

Opening size. Where the area of the floor opening between stories does not exceed twice the horizontal projected area of the escalator or stairway and the opening is protected by a draft curtain and closely spaced sprinklers in accordance with NFPA 13. This application is limited to openings that do not connect more than four stories in buildings not required to have smoke control systems. In buildings that are required to have smoke control systems, escalators are limited to openings that do not connect more than four stories and non-egress stairs are limited to openings that do not atmospherically connect more than two stories.

(Ord. 4524 § 43, 2016: Ord. 4246 § 2 (part), 2010: Ord. 4099 § 3 (part), 2007: Ord. 3946 § 1 (part), 2004)

21.08.050 IBC Section 1104.4 amended.

Section 1104.4 of the IBC is amended to read:

1104.4 Multistory buildings and facilities. At least one accessible route shall connect each accessible level and mezzanine in multilevel buildings and facilities.

(Ord. 4524 § 45, 2016)

21.08.055 IBC Section 1608.1 amended.

Section 1608.1 of the International Building Code is hereby amended to read:

1608.1 General. Design snow loads shall be determined in accordance with Chapter 7 of ASCE 7, but the design roof load shall not be less than that determined by Section 1607. Furthermore, the design roof snow load shall not be less than 25 pounds per square feet. When using this design roof snow load it will be left to the engineer’s judgment whether to consider drift or sliding snow. However, the engineer shall consider a rain on snow surcharge of at least 5 pounds per square feet for roof slopes less than 5 degrees.

(Ord. 4751 § 25, 2021; Ord. 4246 § 2 (part), 2010: Ord. 4099 § 3 (part), 2007: Ord. 3946 § 1 (part), 2004)

21.08.060 IBC Section 1704.12 amended.

Repealed by Ord. 4246. (Ord. 4099 § 3 (part), 2007: Ord. 3946 § 1 (part), 2004)

21.08.070 Penetrations into fire command centers.

Chapter 9 of the IBC is amended and supplemented with the addition of a new Section 911.2 to read as follows:

911.2 Penetrations. Penetrations into and openings through a fire command center are prohibited except for required exit doors, equipment and ductwork necessary for heating, cooling or ventilation, sprinkler branch line piping, electrical raceway for fire department communication and control and electrical raceway serving the fire command center or being controlled from the fire command center. Such penetrations shall be protected in accordance with Section 714.

Exception: Metallic piping with no joints or openings.

(Ord. 4524 § 44, 2016: Ord. 4246 § 2 (part), 2010)

21.08.072 IBC Chapter 27 amended.

User note:

About this chapter: Electrical systems and components are integral to most structures; therefore it is necessary for the code to address their installation and protection. Structures depend on electricity for the operation of many life safety systems including fire alarm, smoke control and exhaust, fire suppression, fire command and communication systems. Since power supply to these systems is essential, Chapter 27 addresses where standby and emergency power must be provided.

Chapter 27 of the IBC is amended to read as follows:

2701.1 Scope.

The provisions of this chapter and the Washington Cities Electrical Code shall govern the design, construction, erection and installation of the electrical components, appliances, equipment and systems used in buildings and structures covered by this code. The International Fire Code, International Building Code, and the Washington Cities Electrical Code shall govern the use and maintenance of electrical components, appliances, equipment and systems. The International Existing Building Code and the Washington Cities Electrical Code shall govern the alteration, repair, relocation, replacement and addition of electrical components, appliances, or equipment and systems.

SECTION 2702

EMERGENCY AND LEGALLY REQUIRED STANDBY POWER SYSTEMS

[F] 2702.1 General.

Emergency power systems and legally required standby power systems shall comply with Sections 2702.1.1 through 2702.1.7 and Table 2702.

[F] 2702.1.1 Stationary generators.

Stationary emergency and legally required standby power generators required by this code shall be listed in accordance with UL 2200.

[F] 2702.1.2 Fuel-line piping protection.

Fuel lines supplying a generator set inside a high-rise building shall be separated from areas of the building other than the room the generator is located in by approved methods:

1.    A fire-resistant pipe-protection system that has been tested in accordance with UL 1489. The system shall be installed as tested and in accordance with the manufacturer’s installation instructions and shall have a rating of not less than 2 hours. Where the building is protected throughout with an automatic sprinkler system installed in accordance with Section 903.3.1.1, the required rating shall be reduced to 1 hour.

2.    An assembly that has a fire-resistance rating of not less than 2 hours. Where the building is protected throughout with an automatic sprinkler system installed in accordance with Section 903.3.1.1, the required fire-resistance rating shall be reduced to 1 hour.

3.    Other approved methods.

[F] 2702.1.3 Installation.

Emergency power systems and legally required standby power systems required by this code or the International Fire Code, systems required by this code or the International Fire Code shall be installed in accordance with the International Fire Code, Washington Cities Electrical Code, NFPA 110 and NFPA 111.

[F] 2702.1.4 Load transfer.

Emergency power systems shall automatically provide secondary power within 10 seconds after primary power is lost, unless specified otherwise in this code. Legally required standby power systems shall automatically provide secondary power within 60 seconds after primary power is lost, unless specified otherwise in this code. Transfer to full emergency or legally required standby power shall take place within the maximum time to energize loads specified in Table 2702.

[F] 2702.1.5 Load duration.

Emergency power systems and legally required standby power systems shall be designed to provide the required power for a minimum duration of 8 hours for fire pumps serving high rise buildings in accordance with NFPA 20, and 2 hours for other systems without being refueled or recharged, unless specified otherwise in this code.

Exception: The minimum duration of all required power loads may be reduced to 2 hours for all systems except for fire pumps that require a minimum duration of 8 hours in accordance with NFPA 20.

[F] 2702.1.6 Uninterruptable power source.

An uninterrupted source of power shall be provided for equipment when required by the manufacturer’s instructions, the listing, this code or applicable referenced standards.

[F] 2702.1.7 Interchangeability.

Emergency power systems shall be an acceptable alternative for installations that require legally required standby power systems.

[F] 2702.1.8 Group I-2 occupancies.

In Group I-2 occupancies, occupancies located in flood hazard areas established in 1612.3, where new essential electrical systems are installed, and where new essential electrical system generators are installed, the systems and generators shall be located and installed in accordance with ASCE 24. Where connections for hookup of temporary generators are provided, the connections shall be located at or above the elevation required in ASCE 24.

[F] 2702.1.9 Equipment room.

If a legally required standby or emergency power system includes a generator set inside or serving a building, the generator set shall be located in a separate room enclosed with 2-hour fire barriers constructed in accordance with Section 707 or horizontal assemblies constructed in accordance with Section 711, or both, to separate it from the remainder of the building, the transfer switches, and from the normal power source including transformers and distribution equipment. The transfer switches shall also be located in a separate room enclosed with 2-hour fire barriers constructed in accordance with Section 707 or horizontal assemblies constructed in accordance with Section 711, or both, to separate it from the remainder of the building. Power distribution from the emergency source to the emergency transfer switch shall be by an independent route from the normal power source. Independent routes shall mean either a physical separation distance of not less than 50 feet, or a minimum of 1-hour fire-resistance rated separation. System supervision with manual start and transfer features shall be provided at the fire command center or an approved location when a fire command center is not required. Such equipment rooms shall be ventilated directly to the exterior for generator combustion air and radiator cooling air. Any ducts required for such ventilation shall not be dampered and shall be fire-resistance rated to the same level of protection as that required for the equipment room. The requirements of this subsection shall not apply to optional tenant-owned or landlord-owned generator sets.

Exception: Transfer switches shall be permitted to be in the same room as the legally required standby or emergency power system generator sets when inside or serving other than: 1) a high-rise building in accordance with Section 403; 2) an underground building in accordance with Section 405; and 3) a hospital in accordance with Section 407.

[F] 2702.1.10 Smoke control power systems.

Smoke control equipment and systems requiring legally required standby or emergency power shall be supplied with two sources of power. Primary power shall be from the normal building power system. Legally required standby power or emergency power shall be from an approved source complying with the Washington Cities Electrical Code. The legally required standby power or emergency power source and its transfer switches shall be in separate rooms from the normal power transformers and switchgears and ventilated directly to and from the exterior. The room shall be completely enclosed in not less than 1-hour fire barriers constructed in accordance with Section 707, or 1-hour horizontal assemblies constructed in accordance with Section 711, or both, except 2-hour fire-resistance construction shall be required for high-rise and underground buildings per Sections 403 and 405 respectively. Power distribution from the two sources shall be by independent routes to the room containing the automatic transfer switch(s). Independent routes shall mean a physical distance of 50 feet or a minimum 1-hour fire-resistance rated separation. Transfer to full emergency power shall be automatic and shall take place within the maximum time to energize loads. The systems shall comply with the Washington Cities Electrical Code.

Exception: Ventilation is not required for rooms containing only transfer switches.

[F] 2702.1.11 Fuel-fired generator sets and fuel storage location.

Fuel fired generator sets and associated fuel storage, including optional landlord-owned or tenant-owned generator sets, located more than 75 feet above the lowest level of Fire Department vehicle access, or located at a floor level more than 30 feet below the lowest level of exit discharge, require the approval of the fire code official.

[F] 2702.2 Where required.

Emergency and legally required standby power systems shall be provided where required by Sections 2702.2.1 through 2702.2.18 and other sections of this code.

[F] 2702.2.1 Ambulatory care facilities.

Essential electrical systems for ambulatory care facilities shall comply with Section 422.6.

[F] 2702.2.2 Elevators and platform lifts.

Legally required standby power shall be provided for elevators and platform lifts used as accessible means of egress as required in Sections 1009.4.1, 1009.5. Emergency power shall be provided for elevators in high-rise buildings as required by Table 2702.

[F] 2702.2.3 Emergency responder radio coverage systems.

Legally Required standby power shall be provided for in-building 2-way emergency responder communication coverage systems required in Section 918 and the International Fire Code. The standby power supply shall be capable of operating the in-building 2-way emergency responder communication coverage system for a duration of not less than 12 hours at 100-percent system operation capacity.

[F] 2702.2.4 Emergency voice/alarm communication systems.

Emergency power shall be provided for emergency voice/alarm communication systems as required in Section 907.5.2.2.5. The system shall be capable of powering the required load for a duration of not less than 24 hours, as required in NFPA 72.

[F] 2702.2.5 Exhaust systems.

Legally required standby power shall be provided for common exhaust systems for domestic kitchens located in multistory structures as required in Section 505.5 of the International Mechanical Code. Legally required standby power shall be provided for common exhaust systems for clothes dryers located in multistory structures as required in Section 504.11 of the International Mechanical Code and Section 614.11 of the International Fuel Gas Code.

[F] 2702.2.6 Exit signs.

Emergency power shall be provided for exit signs as required in Section 1013.6.3. The system shall be capable of powering the required load for a duration of not less than 90 minutes.

[F] 2702.2.7 Gas detection system.

Emergency or legally required standby power shall be provided for gas detection systems in accordance with the International Fire Code.

[F] 2702.2.8 Group I-2 occupancies.

Essential electrical systems for Group I-2 occupancies shall be in accordance with Section 407.11.

[F] 2702.2.9 Group I-3 occupancies.

Emergency power shall be provided for power-operated doors and locks in Group I-3 occupancies as required in Section 408.4.2.

[F] 2702.2.10 Hazardous materials.

Emergency or legally required standby power shall be provided in occupancies with hazardous materials where required by the International Fire Code.

[F] 2702.2.11 High-rise buildings.

Emergency and legally required standby power shall be provided in high-rise buildings as required in Table 2702.

[F] 2702.2.12 Hydrogen fuel gas rooms.

Standby power shall be provided for hydrogen fuel gas rooms as required by the International Fire Code.

[F] 2702.2.13 Laboratory suites.

Legally required standby or emergency power shall be provided in accordance with Section 5004.7 of the International Fire Code where laboratory suites are located above the sixth story above grade plane or located in a story below grade plane.

[F] 2702.2.14 Means of egress illumination.

Emergency power shall be provided for means of egress illumination as required in Section 1008.3. The system shall be capable of powering the required load for a duration of not less than 90 minutes.

[F] 2702.2.15 Membrane structures.

Legally required standby power shall be provided for auxiliary inflation systems in permanent membrane structures as required in Section 3102.8.2. Legally required standby power shall be provided for a duration of not less than 4 hours. Auxiliary inflation systems in temporary air-supported and air-inflated membrane structures shall be provided in accordance with Section 3103.10.4 of the International Fire Code.

[F] 2702.2.16 Semiconductor fabrication facilities.

Emergency power shall be provided for semiconductor fabrication facilities as required in Section 415.11.10.

[F] 2702.2.17 Smoke control systems.

Emergency power shall be provided for smoke control systems as required in Sections 404.7, 909.11, 909.20.6.2 and 909.21.5. Legally required standby power systems shall be provided for pressurization systems in low-rise buildings in accordance with Washington State Building Code Section 504.4.1 and International Building Code Sections 909.20.6 and 909.21.5.

[F] 2702.2.18 Special purpose horizontal sliding, accordion or folding doors.

Legally required standby power shall be provided for special purpose horizontal sliding, accordion or folding doors as required in Section 1010.1.4.3. The standby power supply shall have a capacity to operate not fewer than 50 closing cycles of the door.

[F] 2702.2.19 Underground buildings.

Emergency and legally required power shall be provided in underground buildings as required in Section 405.

[F] 2702.3 Critical circuits.

Critical circuits. Required critical circuits shall be protected using one of the following methods:

1. Cables, used for survivability of required critical circuits, that are listed in accordance with UL 2196 and have a fire-resistance rating of not less than 1 hour.

2. Electrical circuit protective systems having a fire-resistance rating of not less than 1 hour. Electrical circuit protective systems are installed in accordance with their listing requirements.

3. Construction having a fire-resistance rating of not less than 1 hour.

[F] 2702.4 Maintenance.

Emergency and legally required standby power systems shall be maintained and tested in accordance with the International Fire Code.

TABLE 2702

LEGALLY REQUIRED STANDBY AND EMERGENCY POWER 

Type of Equipment

Maximum Time to Energize Loads

Maximum Run Time (Duration)

IBC Section

IFC or NFPA Section

Emergency Power Systems1

Exit illumination

10 seconds

2 hours

1013.6.3

604.2.9 High rises

604.2.16 Underground buildings

1013.6.3 Exit signs

3.4.2.13 Temporary tents, canopies, membrane structures

NFPA 70

Exit illumination

10 seconds

2 hours

1008.3

1008.3

604.2.9 High rises

604.2.16 Underground buildings

Any emergency voice/alarm communication including area of refuge communication systems (barrier-free and horizontal exits)

Per NFPA 72

24 hours (battery)

4 hours (generator)

402.7.3, 402.7.4, and 907.5.2.2 Covered mall buildings

907.2.19 Covered mall buildings

403.4.8 and 907.5.2.2 High rises

604.2.9 High rises

405.8, and 907.5.2.2 Underground buildings

604.2.16 Underground buildings

907.2.1, and 907.5.2.2 Assembly occupancies

907.2.1.1 Assembly occupancies

907.2.11 Special amusement building

NFPA 72

Fire detection and fire alarms

Per NFPA 72

24 hours (battery)

4 hours (generator)

403.4.8 High rises

604.2.9 High rises

405.8 Underground buildings

604.2.16 Underground buildings

909.20.6.2 Smokeproof enclosures

907.6.2

907.2.11 Special amusement building

907

NFPA 72

Smoke control systems in high-rise buildings, underground buildings and covered mall buildings including energy management systems if used for smoke control or smoke removal

60 seconds

2 hours

403.4.8 High rises

909.11

404.7 Atriums

Emergency power

405.8 Underground buildings

 

909.11 Smoke control

 

Fire pumps in high-rise buildings and underground buildings

10 seconds

8 hours (NFPA 20)

403.4.8 High rises

604.2.9 High rises and NFPA 20

405.8 Underground buildings

604.2.16 Underground buildings

 

913.2 All Fire Pumps

Smokeproof enclosures and elevator shaft pressurization

60 seconds for pressurization

4 hours

403.4.8 High rises

 

909 and 909.20.6.2

Any shaft exhaust fans required to run continuously in lieu of dampers in high-rise and underground buildings.

60 seconds

4 hours

717.5.3

 

Fire service or occupant evacuation elevator car operation in high-rise and underground buildings (including control system, motor controller, operation control, signal equipment, machine room cooling-heating, etc.)

 

 

3003, 3007, and 3008

604.2.16 Underground buildings

 

Elevator car lighting and communications in high-rise and underground buildings

10 seconds

4 hours

3003, 3007, and 3008

604.2.9 High rises

304.2.16 Underground Buildings

604.2.1 Elevators

Lights, heating and cooling for building fire command center and mechanical equipment rooms serving the fire command center

60 seconds

24 hours

 

604.2.9 High rises

Power (other than lights, heating and cooling) for building fire command center

60 seconds

4 hours

 

 

Mechanical and electrical systems required by IFC 27 (hazardous materials including UPS rooms)

60 seconds

4 hours

 

Chapter 27

Legally Required Standby1

Exhaust fans for any loading dock located interior to a building

60 seconds

4 hours

 

 

Transfer vault ventilation equipment

60 seconds

4 hours

 

 

Heat tape for sprinkler lines and heating in sprinkler riser rooms

60 seconds

24 hours

 

 

Fuel pump system for any legally required system

60 seconds

4 hours

 

 

Elevators used for accessible means of egress in other than high-rise and underground buildings

60 seconds

2 hours

 

 

Elevators (other than fire service or occupant evacuation elevators) in high-rise and underground buildings

60 seconds

60 seconds

 

 

Any shaft exhaust fans required to run continuously in lieu of dampers (in other than high-rise and underground buildings)

60 seconds

4 hours

717.5.3

 

Auxiliary inflation systems

60 seconds

2 hours

3102.8.2

3103.10.4

Special purpose horizontal sliding, accordion or folding doors

60 seconds

2 hours

1010.1.4.3

1010.1.4.3

Hydrogen fuel gas rooms

60 seconds

2 hours

2702.2.12

5808.7 and 1203

Firefighter air replenishment systems (FARS)

60 seconds

2 hours

919.7.2

919.7.2

TABLE 2702 FOOTNOTE

1.    The fuel pump and associated systems for the emergency or legally required generator shall be provided with power from the generator to maintain fuel supply.

(Ord. 4848 § 28, 2024; Ord. 4751 § 26, 2021; Ord. 4638 § 6, 2018)

21.08.075 IBC Chapter 31 amended.

Chapter 31 of the IBC is amended and supplemented with the addition of a new Section 3116 to read as follows:

Section 3116 OVERWATER STRUCTURES, PIERS, WHARVES, AND BUILDINGS

IBC 3116.1—General. Overwater structures, piers, wharves and buildings shall comply with the requirements of this section and other applicable sections of this code.

IBC 3116.2—Definitions.

OVERWATER STRUCTURES. For the purpose of this Chapter, overwater structures shall include all structures which have twenty percent (20%) or more of their area over water, or a structure which has 8,000 square feet over water.

DOCK. A dock is a natural open or artificially closed basin in which vessels may remain afloat when berthed at a wharf or pier.

PIER. A pier is a structure, usually of greater length than width, of timber, stone, concrete or other material having a deck, and projecting from the shore into navigable waters so that vessels may be moored alongside for loading and unloading or for storage or repairs.

SUBSTRUCTURE. The substructure is that portion of the construction below and including the deck.

SUPERSTRUCTURE. The superstructure is that portion of the construction above the deck.

WHARF OR QUAY. A wharf or quay is a structure of timber, stone, concrete or other material having a platform built along and parallel to navigable waters so that vessels may be moored alongside for loading and unloading, or for storage or repair.

IBC Section 3116.3—Structures over water.

No portion of any building or other structure supported by piers or piling and extending over water shall be more than two hundred fifty feet from an improved public street or alley giving access thereto for fire engines and other firefighting equipment; provided, however, that the foregoing limitation shall not apply to any one-story structure used solely for the moorage of boats and:

(1) Of type 1 construction; or

(2) Of type 2 construction; or

(3) Having installed throughout the structure an approved automatic sprinkler system.

IBC Section 3116.4—Substructure.

1. Draft Stops. Draft stops shall be installed in all substructures constructed of combustible materials, exclusive of piling and pile bracing. They shall be placed not over one hundred feet (100') apart measured along the main axis of the pier or wharf. They shall fit tightly around all joists, beams, etc., and extend from the underside of the deck to low water with a maximum required depth of 6 feet.

EXCEPTION: Private docks which serve a single family dwelling unit.

Substructure draft stops shall be constructed of not less than two (2) thicknesses of 2" nominal thickness lumber laid with broken joints or materials of equal fire resistance.

2. Automatic Sprinklers. Automatic sprinklers shall be installed under the substructure of every overwater structure in accordance with the requirements of Chapter 9.

EXCEPTIONS: Automatic sprinklers are not required under the following categories of substructure:

a. Combustible substructures having superstructures of 120 square feet or less in area.

b. Noncombustible substructures with or without superstructures.

c. Substructures resulting from walkways or finger piers when width does not exceed 10 feet.

3. Dry Standpipes. When a distance of travel to fire apparatus access exceeds two hundred fifty (250) feet, an approved minimum four (4) inch dry standpipe with two and one-half (2-1/2) inch outlets at a maximum of one hundred (100) feet on center shall be provided. There shall be a Siamese connection at the shore end and direct access for Fire Department pumping apparatus shall be provided. Standards for installation to be set by the Director of Fire Services.

Exception: Piers serving no more than one single-family dwelling.

(Ord. 4848 § 29, 2024; Ord. 4246 § 2 (part), 2010: Ord. 4099 § 3 (part), 2007: Ord. 4004 § 4, 2005: Ord. 3946 § 1 (part), 2004)

21.08.105 IBC Section J102 amended.

Repealed by Ord. 4151. (Ord. 4099 § 3 (part), 2007: Ord. 3946 § 1 (part), 2004)

21.08.110 IBC Section J103 amended.

Repealed by Ord. 4151. (Ord. 4099 § 3 (part), 2007: Ord. 4017 § 7, 2005: Ord. 3946 § 1 (part), 2004)

21.08.115 IBC Appendix Section J103.3 added.

Repealed by Ord. 4151. (Ord. 4099 § 3 (part), 2007: Ord. 3946 § 1 (part), 2004)