Chapter 19.11
FIRE CODE

Sections:

19.11.010    General.

19.11.020    International Fire Code adopted.

19.11.030    Appointment.

19.11.040    Board of Appeals.

19.11.050    Permits required.

19.11.060    Permit fees.

19.11.070    Definitions.

19.11.080    Fire alarm and detections systems and related equipment.

19.11.090    Unsafe buildings.

19.11.100    Failure to comply.

19.11.110    Fire apparatus access roads – Dimensions.

19.11.120    Fire Department access roads – Turning radius.

19.11.130    Fire Department access roads – Grade.

19.11.140    Fire Department access roads – Fire lanes.

19.11.150    Fire Department connections – Location.

19.11.160    Fire protections systems – Records.

19.11.170    Automatic sprinkler systems – Group R.

19.11.180    Water supply.

19.11.190    Appendices adopted.

19.11.200    Signage.

19.11.210    Violations and penalties.

19.11.010 General.

Section 103.1 of the International Fire Code is deleted in its entirety and replaced as follows:

Section 103.1 General. The department of fire prevention, also known as the Fire Marshal, is established within the jurisdiction under the direction of the Fire Chief. The function of this department shall be the implementation, administration and enforcement of the provisions of this Code.

[Ord. 2017.04 § 4, 2017].

19.11.020 International Fire Code adopted.

The 2015 Edition of the International Fire Code, published by the International Code Council, including those standards of the National Fire Protection Association specifically referenced in the International Fire Code, and as amended by Chapter 51-54 WAC, and as subsequently amended by this chapter, is hereby adopted along with Appendices B, C, D, F, and G.

Whenever the following words appear in the International Fire Code, they are to be changed as follows:

A. “Chief of the Fire Department,” “Fire Prevention Engineer,” “Enforcement Official,” “Fire Code Official” to “Fire Chief.”

B. “Name of Jurisdiction” or “Jurisdiction” to “City of Wilkeson.”

C. “Corporate Counsel” to “City Attorney.”

D. “Fire Department” to “City of Buckley Fire Department.” [Ord. 2017.04 § 4, 2017].

19.11.030 Appointment.

Section 103.2 of the International Fire Code is deleted in its entirety and replaced as follows:

Section 103.2 Appointment. The Fire Chief shall be appointed by the Mayor.

[Ord. 2017.04 § 4, 2017].

19.11.040 Board of Appeals.

Section 108 of the International Fire Code is hereby repealed. Permit decisions made by the Fire Chief, or their designee, shall be subject to the review and appeal by the City Council. Formal fire code interpretations made by the Fire Chief shall be considered administrative decisions for purposes of appeal rights and responsibilities. [Ord. 2017.04 § 4, 2017].

19.11.050 Permits required.

Section 105.6 of the International Fire Code is amended as follows:

A. Section 105.6.16, Fire Hydrants and Valves, is deleted.

B. Section 105.6.37, Private Fire Hydrants, is deleted. [Ord. 2017.04 § 4, 2017].

19.11.060 Permit fees.

Section 105.8 is added to the International Fire Code to read as follows:

1. Construction Permits. Fees for construction permits for new construction, including but not limited to tenant improvements, shall be based on the number of hours spent by the Fire Chief, or their designee, performing the plan review and fire code inspection. A per hour fee, established by a Resolution of the City Council, shall be assessed in 30-minute increments with the first 30 minutes or any portion thereof charged the full hourly rate.

a. Revocation. The Fire Chief is authorized to suspend or revoke a permit when it is determined that the permittee failed, refused or neglected to pay required fees within 30 days following mailing of an invoice to the permittee requiring payment. Mailing shall be accomplished by first class mail of the U.S. Postal Service.

[Ord. 2017.04 § 4, 2017].

19.11.070 Definitions.

Section 502.1 of the International Fire Code is amended to add the following:

FIRE APPARATUS. Fire apparatus is a vehicle such as a fire pumper, aerial ladder truck, fire tender, elevated platform, rescue squad, fire ground support vehicle or similar fire-fighting or reserve equipment, including emergency medical response vehicles.

[Ord. 2017.04 § 4, 2017].

19.11.080 Fire alarm and detections systems and related equipment.

Section 105.7.6 of the International Fire Code is amended to read as follows:

Section 105.7.6 Fire alarm and detection systems and related equipment. A construction permit is required for installation of or modification to fire alarm and detections systems and related equipment. Maintenance performed in accordance with this code is not considered a modification and does not require a permit.

EXCEPTION: Household fire alarm and detection system equipment installed in Group R-3 occupancies.

[Ord. 2017.04 § 4, 2017].

19.11.090 Unsafe buildings.

Section 110.5 is added to the International Fire Code to read as follows:

Section 110.5 Damaged buildings. The owner, occupant or other person having under their control any property or materials on a property damaged by a fire or explosion shall, when ordered by the Fire Chief, immediately secure the property against entry or unauthorized access by the public, by boarding up all openings, fencing, barricading or utilizing other appropriate measures.

[Ord. 2017.04 § 4, 2017].

19.11.100 Failure to comply.

Section 111.4 of the International Fire Code is deleted in its entirety and replaced as follows:

Section 111.4 Failure to comply. Any person who shall continue any work after having been served with a stop work order, except such work as the person is directed to perform to remove a violation or unsafe condition shall be guilty of a civil infraction as specified in WMC 19.11.210.

[Ord. 2017.04 § 4, 2017].

19.11.110 Fire apparatus access roads – Dimensions.

Section 503.2.1 of the International Fire Code is deleted in its entirety and replaced as follows:

503.2.1 Dimensions. Fire apparatus access roads serving one dwelling unit shall have an unobstructed width of not less than 15 feet, exclusive of shoulders. All other fire apparatus access roads shall have an unobstructed width of not less than 20 feet, exclusive of shoulders. All fire apparatus access road shall have an unobstructed vertical clearance of not less than 13 feet 6 inches. When a fire apparatus access road is required, it shall extend from the public or private road or shared access facility to within 150 feet of all portions of an exterior wall of the first story, as measured in an approved route around the exterior of the building.

[Ord. 2017.04 § 4, 2017].

19.11.120 Fire Department access roads – Turning radius.

Section 503.2.4 of the International Fire Code is deleted in its entirety and replaced as follows:

503.2.4 Turning radius. The required turning radius of a fire apparatus access road shall be not less than 28 feet inside, and not less than 48 feet outside radius.

[Ord. 2017.04 § 4, 2017].

19.11.130 Fire Department access roads – Grade.

Section 503.2.7 of the International Fire Code is deleted in its entirety and replaced as follows:

503.2.7 Grade. The road grade of a fire apparatus access road shall not exceed 12% with a minimum side slope of 2%. All sections of fire apparatus access roads with grades of over 10% shall be paved.

Exception: Side slope may be less than 2% as required or approved by the City Engineer.

[Ord. 2017.04 § 4, 2017].

19.11.140 Fire Department access roads – Fire lanes.

Section 511 is added to the International Fire Code to read as follows:

Section 511.1 Establishment of Fire Lanes. Fire lanes in conformance with this code shall be established by the fire chief or his/her authorized designee, and shall be referred to as designated fire lanes in this section.

Section 511.2 Definition of Fire Lanes. The area within any public right-of-way, easement, or on private property designated for the purpose of permitting fire apparatus use, travel upon, and parking.

Section 511.3 Marking of Fire Lanes. All designated fire lanes shall be clearly marked by signage and/or surface painting as required by the fire chief. Painted identification shall be by a four-inch wide line and block letters two feet high, painted in the lane in bright yellow or bright red, at 50-foot or such other intervals as determined by the fire chief, stating “Emergency Vehicles Only,” and by posting of signs stating, “Emergency Vehicles Only – No Parking – Violator Vehicles Subject to Impound.” Signs shall be posted on or immediately next to the curb line, or on the building. Signs shall be 12 inches by 18 inches and shall have red letters on a white background, readily readable from at least a 50-foot distance. Signs shall be posted no further than 50 feet apart, unless a greater distance is deemed reasonable by the fire chief, nor shall they be more than four feet from the ground unless a greater height is determined necessary by the fire chief.

Section 511.4 Obstruction of Fire Lanes Prohibited. The obstruction of a designated fire lane by a parked vehicle or any other object is prohibited and shall constitute a traffic hazard as defined in state law and an immediate hazard to life and property.

Section 511.5 Maintenance of Fire Lanes. Fire lane markings shall be maintained at the expense of the property owner as often as needed to clearly identify the designated areas as being a fire lane.

Section 511.6 Property Owner Responsible. The owner, manager, or person in charge of any property upon which designated fire lanes have been established shall prevent the parking of vehicles or placement of other obstructions in such fire lanes.

Section 511.7 Violation – Civil Infraction. Any person who fails to mark or maintain the markings of a designated fire lane as prescribed in this chapter, or who parks a vehicle in, allows the parking of a vehicle in, obstructs, or allows the obstruction of a designated fire lane commits a civil infraction. The penalty for failing to mark or maintain the markings of a designated fire lane shall be $150.00. The penalty for parking a vehicle in, allowing the parking of a vehicle in, obstructing, or allowing the obstruction of a designated fire lane shall be $50.00.

Section 511.8 Impoundment. Any vehicle or object obstructing a designated fire lane is hereby declared a traffic hazard and may be abated without prior notification to its owner by impoundment pursuant to the applicable state law.

Section 511.9 Enforcement. The City of Buckley Police Department or any other designated representative of the fire chief shall have authority to enforce the provisions of this code.

[Ord. 2017.04 § 4, 2017].

19.11.150 Fire Department connections – Location.

Section 912.2 of the International Fire Code is deleted in its entirety and replaced as follows:

912.2 Location. With respect to hydrants, driveways, buildings and landscaping, fire department connections shall be so located that fire apparatus and hose connected to supply the system will not obstruct access to the buildings for other fire apparatus. The location of the fire department connection shall be approved by the Fire Chief and shall not be closer than 50 feet from a structure or 1 1/2 times the height of the structure.

[Ord. 2017.04 § 4, 2017].

19.11.160 Fire protections systems – Records.

Section 901.6.2 of the International Fire Code is deleted in its entirety and replaced as follows:

901.6.2 Records. Records of all system inspections, testing and maintenance required by the referenced standards shall be maintained on the premises for a minimum of 3 years. A copy of any inspection, test or maintenance shall be forward to the Fire Chief within 30 days of the service.

[Ord. 2017.04 § 4, 2017].

19.11.170 Automatic sprinkler systems – Group R.

Section 903.2.8 of the International Fire Code is deleted in its entirety and replaced as follows:

903.2.8 Group R. An automatic sprinkler system installed in accordance with Section 903.3 shall be provided for Group R occupancies.

Exception: An automatic sprinkler system is not required in Group R-3 occupancies where the total living space of the building does not exceed 5,000 square feet.

[Ord. 2017.04 § 4, 2017].

19.11.180 Water supply.

Section 3408 of the International Fire Code is amended as follows:

A. Section 3408.1, Water Supply, is deleted. [Ord. 2017.04 § 4, 2017].

19.11.190 Appendices adopted.

2015 IFC Appendix B, Fire-Flow Requirements for Buildings, is amended as follows:

Section B105 of the International Fire Code is deleted in its entirety and replaced as follows:

B105 Fire-Flow requirements for buildings. Prior to the issuance of a building permit for any building, portion of a building, or substantial alteration thereto, fire-flow shall be provided in the amount required by this Section. Fire-flow shall be automatically available and supplied at a residual pressure of not less than 20 pounds per square inch (psi) (138 kPa).

B105.1 One- and Two-family dwellings. The minimum fire-flow requirements for one- and two-family dwellings (Group R-3) having a fire-flow calculation area which does not exceed 3,600 square feet shall be 750 gallons per minute (GPM) for one (1) hour for each hydrant providing fire flow. Fire-flow for buildings of 3,600 square feet or more in floor area including attached garages, covered porches and under upper story decks shall be 1,000 GPM for one (1) hour for each hydrant providing fire flow.

EXCEPTIONS:

a) Fire-protection credits as described in Table B105.2 may be used in lieu of providing minimum fire-flow requirements for one- and two-family dwellings (Group R-3) on lots which are one gross acre or more in area.

b) Fire-protection credits as described in Table B105.2 may be used in lieu of providing minimum fire-flow requirements for one- and two-family dwellings (Group R-3) if a water main capable of providing at least 500 GPM of fire-flow is not available to the building, portion of a building, or substantial alteration thereto. If the above fire-flow can be provided by the addition of a fire hydrant, the fire hydrant shall be installed.

c) When at least 500 GPM is available from an approved fire hydrant, it shall be credited toward the required fire-flow for one- and two-family dwellings (Group R-3). The additional fire-flow requirements may be provided by using fire-protection credits as described in Table B105.2 in lieu of providing additional fire flow.

B105.2 Group U Occupancies. The minimum fire-flow requirements for Group U occupancies shall be 750 GPM for one (1) hour for each hydrant providing fire flow.

EXCEPTIONS:

1. Minimum fire-flow is not required for Group U occupancies meeting all of the following criteria:

a) It does not exceed 2,500 square feet; and

b) It is accessory to a one- or two-family dwelling (Group R-3) that has fire-flow or 100% of fire protection credits as described in Table B105.2; and

c) It has setbacks from side and rear lot lines of at least 20 feet, and is at least 10 feet from other buildings on the same lot.

2. Fire-protection credits as described in Table 105.2 may be used in lieu of providing minimum fire-flow requirements for Group U occupancies on lots which are one gross acre or more in area.

3. Fire-protection credits as described in Table B105.2 may be used in lieu of providing minimum fire-flow requirements for Group U occupancies if a water main capable of providing at least 500 GPM of fire-flow is not available to the building, portion of a building, or substantial alteration thereto. If the above fire-flow can be provided by the addition of a fire hydrant, the fire hydrant shall be installed.

4. When at least 500 GPM is available from an approved fire hydrant, it shall be credited toward the required fire-flow for Group U occupancies. The additional fire-flow requirements may be provided by using fire-protection credits as described in Table B105.2 in lieu of providing additional fire flow.

B105.3 Buildings other than One- and Two-family dwellings (Group R-3) and Group U occupancies. The minimum fire-flow requirements for buildings other than one- and two-family dwellings (Group R-3) and Group U occupancies shall not be less than that specified in Table B105.1 of the International Fire Code (IFC).

EXCEPTIONS:

1. A reduction in required fire-flow of up to 50%, as approved, is allowed when the building is provided with an approved automatic sprinkler system installed in accordance with Section 903.3.1.1 or 903.3.1.2 of the IFC. Where buildings are also of Type I or II construction and are a light-hazard occupancy as defined by NFPA 13, the reduction may be up to 75%. However, the minimum amount of fire-flow required shall at no time be less than 1,500 GPM except as noted in Exception number 2 below. Fire-flow and duration of fire-flow shall be the fire-flow and duration of the actual fire-flow required after reductions for fire protection features described above.

2. When at least 1,000 GPM is available from an existing approved water main, or is provided by the extension of or from an existing water main, it shall be credited toward the required fire-flow. The fire-flow requirement may be reduced to that available by using fire-protection features such as approved monitored automatic sprinkler systems or fire resistive building construction as specified in Table B105.2 in lieu of additional fire-flow. Fire-flow and duration of fire-flow shall be the fire-flow and duration of the actual fire-flow required after reductions for fire protection features described above.

3. Non-combustible fueling station canopies shall be exempt from all fire flow provisions.

TABLE B105.2 

Fire Protection Credits
(1)

Options to reduce Fire-Flow (2)

Group R-3 & U (3)

All Others (3) (4) (5)

% of reduction

% of reduction

Building less than 2,000 sq. ft.

-35%

-25%

Building 2,000 sq. ft. to 3,600 sq. ft.

-20%

n/a

NFPA 13 D extended coverage sprinkler system (6)

-65%

n/a

NFPA 13 D sprinkler system

-50%

n/a

NFPA 13 R sprinkler system

-50%

n/a

Residential Range-top Fire Suppression System

-15%

n/a

NFPA 13 sprinkler system

n/a

-50%

30' minimum setback from property lines (8)

-25%

-15%

Monitored Fire Alarm

-25%

-25%

1-hour construction (7)

-15%

-25%

Class A or B roof

-15%

-10%

60% brick/stone exterior or approved non-combustible exterior

-15%

-10%

(1) Each portion of a building shall be considered as a separate fire area when separated by one or more four-hour fire walls with no openings and a 30-inch parapet, constructed in accordance with the International Building Code (IBC).

(2) Credits used for or with substantial alterations shall be applied to the entire structure.

(3) Types of construction are based upon the IBC.

(4) Shall not apply to IBC Group-H Occupancy classifications.

(5) In Types IA and IB construction, only the three largest successive floor areas shall be used.

(6) Consists of a 13D sprinkler system with sprinkler coverage extended into the garage, attic, small bathrooms and closets, and porch coverings.

(7) Consists of a minimum of “type X” drywall throughout interior for Group R-3 and U occupancies. Other occupancy groups shall meet the requirements for one-hour construction specified by the IBC.

(8) The 30-foot setback is from side and rear property lines. Front setbacks may be allowed by the zoning of the property.

[Ord. 2017.04 § 4, 2017].

19.11.200 Signage.

A new Section 3205.6.1 is hereby added to the fire code, adopted in WMC 19.11.020, which shall read as follows:

A. Section 3205.6.1, Signage.

Facilities designed in accordance with this section shall include the appropriate signage (as shown below) and shall be properly posted as described herein.

Example of approved signage required for use of Section 3205.6.1, as amended:

1. This sign must be posted prior to building being occupied.

2. Mount signs at 50'0" O.C. on all walls starting 25'0" from any exterior corner; also on two sides of each column.

3. Signage required on end of racks, if installed in rows.

B. Additionally, signage shall comply with Section 310.3 of the International Fire Code which requires the fire code official to approve the content, lettering, size, color and location of required “No Smoking” signs.

[Ord. 2017.04 § 4, 2017].

19.11.210 Violations and penalties.

Persons who shall violate a provision of this code or shall fail to comply with any of the requirements thereof or who shall erect, install, alter, repair or do work in violation of the approved construction documents or directive of the building inspector, or of a permit or certificate used under the provisions of this code, shall be guilty of a misdemeanor, punishable by a fine of not more than five hundred dollars ($500.00) or by imprisonment not exceeding one (1) year or both such fine and imprisonment. Each day that a violation continues after due notice has been served shall be deemed a separate offense. [Ord. 2017.04 § 4, 2017].